SPARCcenter2000EPowerSupply
InstallationManual
Part No.: 802-2700-10
Revision -A, April 1995
A Sun Microsystems, Inc. Business
2550 Garcia Avenue
Mountain View, CA 94043 U.S.A.
415 960-1300 FAX 415 969-9131
Przeglądanie stron 0
1 2 3 4 5 6 ... 53 54

Podsumowanie treści

Strona 1 - InstallationManual

SPARCcenter2000EPowerSupplyInstallationManualPart No.: 802-2700-10Revision -A, April 1995 A Sun Microsystems, Inc. Business2550 Garcia AvenueMountain

Strona 2

x SPARCserver2000E Power SupplyInstallationManual—April1995RelatedDocumentsThe following documents contain information that may be helpful after theup

Strona 3 - Contents

Preface xiWhatTypographicChangesMeanThe following table describes the typographic changes used in this book.ShellPromptsinCommandExamplesThe following

Strona 4

xii SPARCserver2000E Power SupplyInstallationManual—April1995Notes,Cautions,andWarningsWarning – This equipment contains lethal voltage. Accidental co

Strona 5

1-1BeforeYouStart1This manual provides procedures for installing a power supply in a redundant-capable SPARCcenter 2000 or 2000E system cabinet.1.1 Sa

Strona 6

1-2 SPARCserver2000E Power SupplyInstallationManual—April19951To protect both yourself and the equipment, observe the following precautions:1.2 Symbol

Strona 7

BeforeYou Start 1-31CAUTION Riskof equipmentdamage. Toreducethe risk, follow the instructions.AC A terminal to which alternatingcurrent or voltage may

Strona 8

1-4 SPARCserver2000E Power SupplyInstallationManual—April19951Warning – This equipment contains lethal voltages. Accidental contact canresult in serio

Strona 9 - HowThisBookIsOrganized

2-1PowerSupplyInstallation2This chapter provides the complete upgrade procedures.Warning – Risk of electric shock. Do not work inside the cabinet whil

Strona 10 - RelatedDocuments

2-2 SPARCserver2000E Power SupplyInstallationManual—April199522.1 OperatingSystemThe correct operating system must be installed to support dual power

Strona 11 - ShellPromptsinCommandExamples

PowerSupply Installation 2-32Figure 2-1 Key Switch PositionsFigure 2-2 AC Distribution Unit Power SwitchStandbyOnSecureDiagnosticsMain Power↓Off

Strona 12 - Notes,Cautions,andWarnings

PleaseRecycle 1995SunMicrosystems,Inc.2550GarciaAvenue,MountainView,California94043-1100U.S.A.Allrights reserved.This productandrelateddocumentationa

Strona 13 - BeforeYouStart

2-4 SPARCserver2000E Power SupplyInstallationManual—April199522.4 AccessRemove all system cover panels before proceeding with the upgrade. For thesepr

Strona 14 - 1.2 Symbols

PowerSupply Installation 2-522.5.2 Installing the Supply2.5.2.1 Preparation1. Remove the power supply compartment EMI panel Part No. 340-3134-xxcoveri

Strona 15 - BeforeYou Start 1-3

2-6 SPARCserver2000E Power SupplyInstallationManual—April19952Figure 2-4 Disconnecting the Top Power Supply Power Cord3. Remove the power supply cage

Strona 16 - 1.3 ToolsRequired

PowerSupply Installation 2-72Figure 2-5 Removing the Power Supply Cage Cover PanelRemovetheAC Distribution Unit1. Disconnect all AC cables plugged int

Strona 17 - PowerSupplyInstallation

2-8 SPARCserver2000E Power SupplyInstallationManual—April19952Note – J3 is located on the top of the AC distribution unit, J2 is on the backside.2. Re

Strona 18 - 2.3 PoweringDowntheSystem

PowerSupply Installation 2-92FilterCable1. Free the filter cable.a. On the inside of the power supply cage, cut the tie wrap and uncoil thecable. See

Strona 19

2-10 SPARCserver2000E Power SupplyInstallationManual—April199523. Shove the supply into the cavity — flush against the sheet metal in theleft-interior

Strona 20 - 2.4 Access

PowerSupply Installation 2-112Figure 2-10 Installing the Power Supply Mounting ScrewsScrews (6 places)

Strona 21 - 2.5.2 Installing the Supply

2-12 SPARCserver2000E Power SupplyInstallationManual—April199525. Install the bottom cover panel.Position the panel Part No. 340-3190-xx and install 1

Strona 22 - Power cord

PowerSupply Installation 2-132Figure 2-12 Installing the Main Bus Bar2.5.2.4 PowerHarnessInstallationInstall the power harness, Part No. 530-2164-xx (

Strona 23 - RemovetheAC Distribution Unit

iiiContents1. Before You Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11.1 Safety Precautions . . . . . . . .

Strona 24 - RemovetheBreakerBox

2-14 SPARCserver2000E Power SupplyInstallationManual—April19952Figure 2-13 Installing Power Harness on the Top and Bottom Power Supply TerminalBlocksF

Strona 25 - FilterCable

PowerSupply Installation 2-1522.5.2.5 CablingFilterCable,BreakerBoxand AC Distribution Unit1. Plug in the filter cable.Form a service loop in the cabl

Strona 26 - See Figure 2-9

2-16 SPARCserver2000E Power SupplyInstallationManual—April19952d. Place the breaker box against power supply cage.Align the captive screws with the bo

Strona 27 - Screws (6 places)

PowerSupply Installation 2-172b. Replace the three Phillips screws and two #6-32 Phillips screws.c. Replace cables in connectors J2 and J3.1. Plug in

Strona 28 - Screws (12 places)

2-18 SPARCserver2000E Power SupplyInstallationManual—April199522.5.2.6 PowerSupplySenseCable1. Remove the jumper-connector from the power supply adapt

Strona 29

PowerSupply Installation 2-1922.5.2.7 RestoretheSystem1. Replace the power supply compartment EMI panel. See Figure 2-3.Position the panel against the

Strona 30

2-20 SPARCserver2000E Power SupplyInstallationManual—April199522.6 RestartingtheSystemNote – As the system starts up, watch for error messages from th

Strona 31 - 2.5.2.5 Cabling

PowerSupply Installation 2-212Figure 2-20 Local/Remote Switch LocationCaution – Never move the system cabinet or the expansion cabinets whensystem pow

Strona 32 - Screws (2 places, hidden)

2-22 SPARCserver2000E Power SupplyInstallationManual—April199526. Watch the terminal screen for any POST error messages.At the conclusion of testing,

Strona 33

PowerSupply Installation 2-232Figure 2-21 System Reset Switch8. If the system displays “not responding” or “no carrier” messages, theLink Integrity Te

Strona 34 - 2.5.2.6 PowerSupplySenseCable

iv SPARCserver 2000E Power Supply Installation Manual—April 1995A.1 Removal Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-

Strona 35 - 2.5.2.7 RestoretheSystem

2-24 SPARCserver2000E Power SupplyInstallationManual—April19952Note – The following screen display is an example only. The actual messagedisplayed on

Strona 36 - 2.6 RestartingtheSystem

PowerSupply Installation 2-252Figure 2-23 Power Supply Adapter Board LEDsTable 2-1 LED Status IndicatorsLocation LED ConditionFront panel Left LED(gre

Strona 37 - PowerSupply Installation 2-21

2-26 SPARCserver2000E Power SupplyInstallationManual—April19952

Strona 38

A-1AccessAA.1 RemovalProceduresRemove panels to afford access to the power supplies and related components.A.1.1 Opening the Hinged Door1. Grasp the d

Strona 39 - 2.7 ReadingBootMessages

A-2 SPARCserver2000E Power SupplyInstallationManual—April1995AFigure 1-1 Opening the Hinged DoorA.1.2 Removing the Vented Front Panels1. Grasp the pan

Strona 40

Access A-3AFigure 1-2 Removing the Vented Front PanelsA.1.3 Removing the Side PanelsTo remove the left and right side panels:1. Loosen two slot-head c

Strona 41

A-4 SPARCserver2000E Power SupplyInstallationManual—April1995A3. Lift the panel up until free of the tabs at the top of the chassis.Set the panel asid

Strona 42

Access A-5AFigure 1-4 Removing the EMI ShieldA.1.5 Rear Screen Panel1. Remove the two #10 Phillips screws securing the panel to the frame.See Figure 1

Strona 43 - A.1 RemovalProcedures

A-6 SPARCserver2000E Power SupplyInstallationManual—April1995A2. Tilt the panel top out and lift it free of the chassis. Set the panel aside.There is

Strona 44 - See Figure 1-2

Access A-7AA.2.3 Vented Front Panel♦ Place the panel against the chassis with ball studs aligned with catches onthe panel.At both ends, tap or press t

Strona 45 - 2. Tilt the panel bottom out

vFiguresFigure 2-1 Key Switch Positions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3Figure 2-2 AC Distribution Unit Power

Strona 46 - A.1.4 Removing the EMI Shield

A-8 SPARCserver2000E Power SupplyInstallationManual—April1995A

Strona 47 - A.1.5 Rear Screen Panel

RevisionHistoryRevision Dash Date Comments802-2700-10 -A April 1995 First Customer Ship

Strona 48 - A.2 ClosingtheSystem

SPARCserver2000E Power SupplyInstallationManual—April1995

Strona 49 - A.2.4 Side Panels

Reader CommentsWe welcome your comments and suggestions to help improve this manual. Please let usknow what you think about the SPARCserver 2000E Powe

Strona 50

NO POSTAGENECESSARYIF MAILEDIN THEUNITED STATESBUSINESS REPLY MAILFIRST CLASS MAIL PERMIT NO. 1 MOUNTAIN VIEW, CAPOSTAGE WILL BE PAID BY ADDRESSEESUN

Strona 51 - RevisionHistory

vi SPARCserver 2000E Power Supply Installation Manual—April 1995Figure 2-17 Connecting the Power Cords. . . . . . . . . . . . . . . . . . . . . . . .

Strona 52

viiTablesTable 1-1 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2Table 2-1 LED Status Indicators . .

Strona 53 - Reader Comments

viii SPARCserver 2000E Power Supply Installation Manual—April 1995

Strona 54 - BUSINESS REPLY MAIL

ixPrefaceThis manual provides instructions for installing a power supply in aredundant-capable SPARCcenter™2000™or SPARCcenter 2000E™system.These inst