Sun Netra
CP3220 Blade Server
User’s Guide
Part No. 820-1982-12
January 2010, Revision 01
Przeglądanie stron 0
1 2 3 4 5 6 ... 134 135

Podsumowanie treści

Strona 1 - User’s Guide

Sun Microsystems, Inc.www.sun.comSubmit comments about this document at: http://www.sun.com/hwdocs/feedbackSun Netra™CP3220 Blade ServerUser’s GuidePa

Strona 2

x Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 4-1 BIOS Main Menu 4–6FIGURE 4-2 Boot Settings Menu 4–7FIGURE 4-3 Boot Device Priori

Strona 3 - Contents

5-6 Sun Netra CP3220 Blade Server User’s Guide • January 20105.4.2 PCI Express BusPCI Express 1.0 (PCIe) is a high-speed, point-to-point dual simplex

Strona 4 - ▼ To Install an ARTM 10

Chapter 5 Hardware Architecture 5-75.4.6 Sun Dual 10-Gbit Ethernet/Quad 1-Gbit RGMIINetwork Interface Chip (Sun 10 GbEMultithreaded Networking ASIC)Th

Strona 5 - ▼ Setting OOS LED Behavior 35

5-8 Sun Netra CP3220 Blade Server User’s Guide • January 20105.5.2 EIDE/ATA for Compact FlashEIDE is an enhanced IDE controller, implemented through t

Strona 6

A-1APPENDIXAPhysical CharacteristicsSpecifications for the Sun Netra CP3220 blade server are provided in the followingsections: Section A.1, “Form Fa

Strona 7 - Contents vii

A-2 Sun Netra CP3220 Blade Server User’s Guide • January 2010A.1 Form FactorThe Sun Netra CP3220 blade server is a standard 8-rack unit (8U) factor, s

Strona 8

Appendix A Physical Characteristics A-3A.2.2 PICMG Board Cooling RequirementsTABLE A-1 provides the blade server board cooling requirements. No alarms

Strona 9

A-4 Sun Netra CP3220 Blade Server User’s Guide • January 2010A.3 Connectors and PinoutsA.3.1 Front Panel ConnectorsThe front panel has the following c

Strona 10

Appendix A Physical Characteristics A-5A.3.1.2 USB PortsFIGURE A-2 shows the connector pin assignments for both of the front panel USBports.FIGURE A-2

Strona 11 - Figures xi

A-6 Sun Netra CP3220 Blade Server User’s Guide • January 2010A.3.1.3 Serial PortFIGURE A-3 shows the connector pin assignments for the front panel ser

Strona 12

Appendix A Physical Characteristics A-7 Two -48 VDC power feeds (four signals each; eight signals total) Two IPMB ports (two signals each; four sign

Strona 13

Figures xiFIGURE B-18 Boot Device Priority Menu B–11FIGURE B-19 Boot Hard Disk Drive Priority Menu B–11FIGURE B-20 Security Settings Menu B–12FIGURE B

Strona 14

A-8 Sun Netra CP3220 Blade Server User’s Guide • January 201013 SCL_A IPMB Clock, Port A14 SDA_A IPMB Data, Port A15 SCL_B IPMB Clock, Port B16 SDA_B

Strona 15

Appendix A Physical Characteristics A-9A.3.4 Data Transport Connector (Zone 2)The data transport connector consists of two 120-pin HM-Zd connectors, l

Strona 16 - Shell Prompts

A-10 Sun Netra CP3220 Blade Server User’s Guide • January 2010A.3.5 Advanced Rear Transition Module Connector(Zone 3)The Sun Netra CP3220 blade server

Strona 17 - Related Documentation

Appendix A Physical Characteristics A-11TABLE A-8 shows the J31 connector pin assignments, used for AMC I/O signals.TABLE A-8 J31 Connector Pin Assign

Strona 18 - Sun Welcomes Your Comments

A-12 Sun Netra CP3220 Blade Server User’s Guide • January 2010TABLE A-9 shows the J32 connector pin assignments, which are used forinfrastructure sign

Strona 19 - Introduction

B-1APPENDIXBBIOS ScreensThis appendix provides examples of the first-level and second-level screens from theBIOS menu. To enter the BIOS menu, press t

Strona 20 - 1.2 Features

B-2 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE B-1 BIOS Menu TreeAdvancedMain PCI/PnP Boot Security ChipsetCPUConfigurationIDECon

Strona 21 - 1.3 Physical Description

Appendix B BIOS Screens B-3FIGURE B-2 BIOS Main MenuFIGURE B-3 Advanced Configuration Menu

Strona 22 - Figure Leg end

B-4 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE B-4 CPU Configuration MenuFIGURE B-5 IDE Configuration Menu

Strona 23 - Chapter 1 Introduction 1-5

Appendix B BIOS Screens B-5FIGURE B-6 Super IO Configuration MenuFIGURE B-7 ACPI Settings Menu

Strona 24 - 1.3.2 Blade Server Diagram

xii Sun Netra CP3220 Blade Server User’s Guide • January 2010

Strona 25 - 1.4 System Configurations

B-6 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE B-8 Event Logging Details MenuFIGURE B-9 MPS Configuration Menu

Strona 26 - FIGURE 1-6)

Appendix B BIOS Screens B-7FIGURE B-10 PCI Express Configuration MenuFIGURE B-11 SMBIOS Configuration Menu

Strona 27 - Chapter 1 Introduction 1-9

B-8 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE B-12 Remote Access Configuration MenuFIGURE B-13 USB Configuration Menu

Strona 28 - TABLE 1-1. Sun

Appendix B BIOS Screens B-9FIGURE B-14 Advanced PCI/PnP Settings MenuFIGURE B-15 Advanced PCI/PnP Settings Menu Continued

Strona 29 - I/O Configurations

B-10 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE B-16 Boot Settings MenuFIGURE B-17 Boot Settings Configuration Menu

Strona 30 - 1.6 System Components

Appendix B BIOS Screens B-11FIGURE B-18 Boot Device Priority MenuFIGURE B-19 Boot Hard Disk Drive Priority Menu

Strona 31 - 1.6.3 Software Components

B-12 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE B-20 Security Settings MenuFIGURE B-21 Change Password Settings Menu

Strona 32 - Information

Appendix B BIOS Screens B-13FIGURE B-22 Chipset Main MenuFIGURE B-23 NorthBridge Chipset Configuration Menu

Strona 33 - Chapter 1 Introduction 1-15

B-14 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE B-24 NorthBridge Chipset Memory Configuration MenuFIGURE B-25 NorthBridge Chipset

Strona 34

Appendix B BIOS Screens B-15FIGURE B-26 NorthBridge Chipset DRAM Configuration MenuFIGURE B-27 SouthBridge Chipset Configuration Menu

Strona 35

xiiiTablesTABLE 1-1 I/O Configurations 1–11TABLE 2-1 Local Area Network Information 2–5TABLE 2-2 Netinstall Boot Device Table 2–15TABLE 2-3 Extra MAC

Strona 36 - ■ A ground mat

B-16 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE B-28 Hyper Transport Configuration MenuFIGURE B-29 Exit Options Menu

Strona 37

Appendix B BIOS Screens B-17

Strona 38 - Requirements

Index-1IndexAAdvanced PCI/PnP Settings menu, B-9Airflow Requirements, A-3AMC connectors, A-6AMC devicesadditional I/O, 1-7installing, 2-26AMC.1 Type 4E

Strona 39

Index-2 Sun Netra CP3220 Blade Server User’s Guide • January 2010contacting support, 1-14CPU Configuration menu, B-4Ddata transport connector, A-9DDR-2

Strona 40

Index-3hardware, 1-13safety, 2-2software, 1-13revision number, locating, 1-14RJ-45 Ethernet, A-4RTM Pressure Drop, A-3SSecurity Settings menu, B-12ser

Strona 41

Index-4 Sun Netra CP3220 Blade Server User’s Guide • January 2010

Strona 42

xiv Sun Netra CP3220 Blade Server User’s Guide • January 2010

Strona 43

xvPrefaceThe Sun Netra CP3220 Blade Server User’s Guide describes the hardware specifications,function, and physical properties of the Sun Netra™ CP32

Strona 44 - ▼ To Install an ARTM

xvi Sun Netra CP3220 Blade Server User’s Guide • January 2010Using UNIX CommandsThis document might not contain information about basic UNIX®commands

Strona 45

Preface xviiTypographic ConventionsRelated DocumentationThe following table lists the documentation for this product. Except for the ImportantSafety I

Strona 46 - FIGURE 2-2)

xviii Sun Netra CP3220 Blade Server User’s Guide • January 2010Documentation, Support, and TrainingThird-Party Web SitesSun is not responsible for the

Strona 47

1-1CHAPTER1IntroductionThis chapter provides an overview of the features, configurations, and systemrequirements of the Sun Netra CP3220 blade server.

Strona 48 - The minicom utility

PleaseRecycleCopyright © 2010 Sun Microsystems, Inc., 4150 Network Circle, Santa Clara, California 95054, U.S.A. All rights reserved.This distribution

Strona 49 - Solaris OS

1-2 Sun Netra CP3220 Blade Server User’s Guide • January 20101.1 OverviewThe Sun Netra CP3220 blade server is a high-performance, single-board compute

Strona 50

Chapter 1 Introduction 1-3 E-IDE master to support one Compact Flash socket supporting up to 16-Gbyteuser flash (accessible when blade is removed fro

Strona 51 - 2.3 Service Procedures

1-4 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 1-1 Sun Netra CP3220 Dual-Core Blade Server (Front View)Figure Leg end1 Locking sc

Strona 52 - 2.3.4 Powering On the System

Chapter 1 Introduction 1-5FIGURE 1-2 Sun Netra CP3220 Quad-Core Blade Server (Front View)Figure Leg end1 Locking screws 6 Reset button2 Latches 7 10/1

Strona 53 - 2.3.6 Servicing DIMMs

1-6 Sun Netra CP3220 Blade Server User’s Guide • January 20101.3.2 Blade Server DiagramFIGURE 1-3 Sun Netra CP3220 Blade Server (Component Side View)F

Strona 54

Chapter 1 Introduction 1-71.4 System ConfigurationsSun Netra CP3220 blade servers can be installed into an ATCA shelf (chassis), asshown inFIGURE 1-4.

Strona 55 - FIGURE 2-5)

1-8 Sun Netra CP3220 Blade Server User’s Guide • January 20101.4.2 Advanced Rear Transition ModuleYou can install an optional Sun Netra CP32x0 Advance

Strona 56 - 2.3.6.3 Removing a DDR2 DIMM

Chapter 1 Introduction 1-9Note – Use only serial cables that are less than 10 meters in length.FIGURE 1-6 shows the physical relationship between the

Strona 57 - Removing a DIMM

1-10 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 1-6 Sun Netra CP3220 Blade Server, Backplane, and Relationship to ARTMNote – When

Strona 58 - FIGURE 2-7)

Chapter 1 Introduction 1-1110/100/1000BASE-T per second Ethernet RJ-45 port from the host to the rear of thesystem. This port can be used to accomplis

Strona 59 - Compact Flash Location

iiiContentsPreface xv1. Introduction 1–11.1 Overview 1–21.2 Features 1–21.3 Physical Description 1–31.3.1 Front Panel Components 1–31.3.2 Blade Server

Strona 60 - FIGURE 2-8

1-12 Sun Netra CP3220 Blade Server User’s Guide • January 20101.5 Hot-Swap SupportIn general, the hot-swap process includes the orderly connection of

Strona 61 - Removing an AMC Filler Panel

Chapter 1 Introduction 1-13Caution – You can damage the Sun Netra CP3220 blade server components if youinstall the blade server in a chassis that does

Strona 62 - Installing an AMC Card

1-14 Sun Netra CP3220 Blade Server User’s Guide • January 20101.7 Technical Support and WarrantyShould you have any technical questions or support iss

Strona 63

Chapter 1 Introduction 1-15FIGURE 1-7 Sun Netra CP3220 Blade Server Barcode LabelingPart number label Serial numberlabel

Strona 64 - Pin Number Purpose

1-16 Sun Netra CP3220 Blade Server User’s Guide • January 2010

Strona 65

2-1CHAPTER2Hardware Installation and ServiceThis chapter describes the Sun Netra CP3220 blade server hardware installation andservice procedures.This

Strona 66

2-2 Sun Netra CP3220 Blade Server User’s Guide • January 20102.1 Safety and Tool Requirements2.1.1 Equipment and Operator SafetyRefer to the Important

Strona 67

Chapter 2 Hardware Installation and Service 2-3The grounded mat or the chassis must be connected to a facility ground toprevent a floating ground. Ke

Strona 68 - ▼ Viewing OOS LED Settings

2-4 Sun Netra CP3220 Blade Server User’s Guide • January 20104. Verify that local area network (LAN) preparations are completed (seeSection 2.2.1.2, “

Strona 69 - ▼ Setting OOS LED Behavior

Chapter 2 Hardware Installation and Service 2-52.2.1.2 Local Network IP Addresses and Host Names WorksheetCollect the information listed in TABLE 2-1

Strona 70 - Reset button

iv Sun Netra CP3220 Blade Server User’s Guide • January 20102. Hardware Installation and Service 2–12.1 Safety and Tool Requirements 2–22.1.1 Equipmen

Strona 71 - Software Configuration

2-6 Sun Netra CP3220 Blade Server User’s Guide • January 20102.2.1.3 Installation Procedure SummaryThis section summarizes the high-level procedures t

Strona 72 - 3.2 Software Updates

Chapter 2 Hardware Installation and Service 2-72.2.2.1 Verify Chassis Fan Tray UpgradeCaution – The Sun Netra CT 900 server fan tray upgrade kit (594-

Strona 73 - 3.3 SunVTS Software

2-8 Sun Netra CP3220 Blade Server User’s Guide • January 20102.2.2.3 Configuring the Advanced Rear Transition Module HardwareIf you are using a Sun Ne

Strona 74

Chapter 2 Hardware Installation and Service 2-9FIGURE 2-1 Installing the Sun Netra CP32x0 ARTM

Strona 75 - Behavior

2-10 Sun Netra CP3220 Blade Server User’s Guide • January 2010▼ To Install an ARTM1. Verify that you have taken the necessary antistatic precautions.S

Strona 76 - Data Bytes

Chapter 2 Hardware Installation and Service 2-11FIGURE 2-2 Injector/Ejector Latch and Locking Screw on the ARTM6. Carefully align the edges of the ART

Strona 77

2-12 Sun Netra CP3220 Blade Server User’s Guide • January 201010. Install the Sun Netra CP3220 blade server into the front of the ATCA shelf inthe cor

Strona 78

Chapter 2 Hardware Installation and Service 2-132.2.4 Connecting External I/O CablesFront panel ports are typically used for maintenance and troublesh

Strona 79 - Firmware

2-14 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 2-3 Serial Port on the Sun Netra CP3220 Blade Server3. Use one of the following t

Strona 80 - 4.1 About BIOS Settings

Chapter 2 Hardware Installation and Service 2-15 A telnet utility (Connect to the proper port on a Network Terminal Server towhich the Sun Netra CP32

Strona 81 - BIOS Setup Screens Summary

Contents v2.3.4 Powering On the System 2–182.3.5 Automatic Power-Off Events 2–182.3.6 Servicing DIMMs 2–192.3.6.1 DIMM Requirements 2–192.3.6.2 Instal

Strona 82 - Menu Item

2-16 Sun Netra CP3220 Blade Server User’s Guide • January 2010The Sun Netra CP3220 blade server supports virtual LAN configuration for the Sun10 GbE M

Strona 83 - Setup Screens

Chapter 2 Hardware Installation and Service 2-172.3 Service Procedures2.3.1 Hot-Swapping the Sun Netra CP3220 Blade ServerYou can remove the Sun Netra

Strona 84

2-18 Sun Netra CP3220 Blade Server User’s Guide • January 20102.3.3 Removing the Sun Netra CP3220 Blade Server1. Power off the Sun Netra CP3220 blade

Strona 85

Chapter 2 Hardware Installation and Service 2-192.3.6 Servicing DIMMs2.3.6.1 DIMM RequirementsThe Sun Netra CP3220 blade server supports a total of ei

Strona 86

2-20 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 2-4 Locating DIMM SlotsPopulate DIMMs in matching pairs, starting with Pair 0, th

Strona 87 - FIGURE 4-4)

Chapter 2 Hardware Installation and Service 2-212.3.6.2 Installing a DDR2 DIMMThe following procedure provides a general guide for installing addition

Strona 88 - Change Password Menu

2-22 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 2-5 Installing a DIMM6. Press the top edge of the DIMM toward the blade server un

Strona 89 - FIGURE 4-5)

Chapter 2 Hardware Installation and Service 2-23If an ESD mat is not available, you can place the blade server on the antistaticenvelope in which it w

Strona 90 - 4.8 Secondary BIOS Image

2-24 Sun Netra CP3220 Blade Server User’s Guide • January 20102.3.7 Installing the Optional Compact Flash CardAn IDE Compact Flash card can be install

Strona 91

Chapter 2 Hardware Installation and Service 2-25FIGURE 2-7 Compact Flash LocationNote – Sun Compact Flash cards have a life time of 2,000,000 write/er

Strona 92 - 4.12 Changing POST Options

vi Sun Netra CP3220 Blade Server User’s Guide • January 20104. Configuring and Using BIOS Firmware 4–14.1 About BIOS Settings 4–24.1.1 Navigating BIOS

Strona 93 - POST Options

2-26 Sun Netra CP3220 Blade Server User’s Guide • January 20102.3.8 Installing Optional AMC CardsAn Advanced Mezzanine card (AMC) is a card or module

Strona 94

Chapter 2 Hardware Installation and Service 2-27FIGURE 2-8 Removing an AMC Filler Panel4. Retrieve the AMC module from its shipping kit and place it o

Strona 95 - Hardware Architecture

2-28 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 2-9 Installing an AMC CardCaution – Do not use excessive force when installing th

Strona 96 - 5.1 Block Diagram

Chapter 2 Hardware Installation and Service 2-297. Press on the front face of the AMC card until the card is fully seated into theAMC connector.8. Pre

Strona 97 - 5.2 The AMD Opteron Processor

2-30 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 2-10 Jumper 1 in the Run PositionTABLE 2-4 provides information on the pin functi

Strona 98 - 5.3 Memory

Chapter 2 Hardware Installation and Service 2-31To reset the jumper and return the CMOS settings to the default settings, performthe following steps:1

Strona 99 - 5.4 Networking and I/O

2-32 Sun Netra CP3220 Blade Server User’s Guide • January 20102.3.10.2 Changing the OOS LED ColorThe color of the Out-of-service (OOS) LED can be set

Strona 100 - 5.4.3 Dual BIOS

Chapter 2 Hardware Installation and Service 2-33Users can change the default behavior of the out-of-service (OOS) LED through theIPMC by using an LED1

Strona 101 - 5.5 I/O Components

2-34 Sun Netra CP3220 Blade Server User’s Guide • January 2010▼ Viewing OOS LED Settings● At the clia CLI, enter the Get IPMI Control Bits command.Dat

Strona 102 - 5.5.3 SAS/SATA

Chapter 2 Hardware Installation and Service 2-35▼ Setting OOS LED BehaviorNote – You must always perform a read, modify, and write to change any of th

Strona 103 - Physical Characteristics

Contents vii5.4.5 Broadcom 5715C Gigabit Ethernet 5–65.4.6 Sun Dual 10-Gbit Ethernet/Quad 1-Gbit RGMII Network InterfaceChip (Sun 10 GbE Multithreaded

Strona 104 - A.1 Form Factor

2-36 Sun Netra CP3220 Blade Server User’s Guide • January 20102.3.12 Resetting the Sun Netra CP3220 Blade ServerCaution – Do not operate the ATCA shel

Strona 105 - ARTM Pressure Drop

3-1CHAPTER3Software ConfigurationThis chapter provides procedures and information about configuring the software.This chapter contains the following t

Strona 106 - A.3 Connectors and Pinouts

3-2 Sun Netra CP3220 Blade Server User’s Guide • January 20103.1 Operating SystemsThe Sun Netra CP3220 blade server has been tested for compatibility

Strona 107 - A.3.1.2 USB Ports

Chapter 3 Software Configuration 3-33.3 SunVTS SoftwareNote – The Sun Validation Test Suite (SunVTS software) runs on the Solaris OS only.There are si

Strona 108 - A.3.2 AMC Connectors

3-4 Sun Netra CP3220 Blade Server User’s Guide • January 20103.4 Configuring Sun Netra CP3220 For 1GbEor 10GbE SwitchesThe extended fabric on the Sun

Strona 109 - Pin Number Name Description

Chapter 3 Software Configuration 3-53.5 Configuring Alternate OOS LEDBehaviorAdministrators and service technicians can change the default behavior of

Strona 110

3-6 Sun Netra CP3220 Blade Server User’s Guide • January 2010▼ Displaying Configuration of OOS LED BehaviorUse the following command to display the cu

Strona 111 - Zone 2 Connector

Chapter 3 Software Configuration 3-7▼ Setting Configuration of OOS LED BehaviorUse the following command to set the configuration of OOS LED behavior.

Strona 112 - (Zone 3)

3-8 Sun Netra CP3220 Blade Server User’s Guide • January 2010

Strona 113 - J31 Connector Pin Assignments

4-1CHAPTER4Configuring and Using BIOSFirmwareThis chapter describes how to use the BIOS (Basic Input Output System) to configurethe blade server.This

Strona 114 - J33 Connector Pin Assignments

viii Sun Netra CP3220 Blade Server User’s Guide • January 2010

Strona 115 - BIOS Screens

4-2 Sun Netra CP3220 Blade Server User’s Guide • January 20104.1 About BIOS SettingsThis section describes how to view and modify the BIOS settings.Th

Strona 116 - FIGURE B-1 BIOS Menu Tree

Chapter 4 Configuring and Using BIOS Firmware 4-34.1.2.2 AMD PowerNow! Feature Enabled by DefaultThe AMD PowerNow! feature, which is accessed from the

Strona 117 - Advanced Configuration Menu

4-4 Sun Netra CP3220 Blade Server User’s Guide • January 20104.2 Changing the Configuration of a BIOSMenu ItemYou can change the BIOS configuration by

Strona 118 - IDE Configuration Menu

Chapter 4 Configuring and Using BIOS Firmware 4-54.3 Setting the Boot Device Using BIOSSetup ScreensBefore beginning this procedure, ensure that you h

Strona 119 - ACPI Settings Menu

4-6 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 4-1 BIOS Main Menu5. Using the arrow keys, move across the top of the screen to th

Strona 120 - MPS Configuration Menu

Chapter 4 Configuring and Using BIOS Firmware 4-7FIGURE 4-2 Boot Settings Menu6. Move down the list, select the Boot Device Priority option, and press

Strona 121 - SMBIOS Configuration Menu

4-8 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 4-3 Boot Device Priority Menu7. Select the NVIDIA Boot Agent device as the 1st Boo

Strona 122 - USB Configuration Menu

Chapter 4 Configuring and Using BIOS Firmware 4-94.4 Changing the BIOS Continuous BootSettingTraditionally, the BIOS of a PC would go through the list

Strona 123 - Appendix B BIOS Screens B-9

4-10 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 4-4 Security Settings MenuFIGURE 4-5 Change Password Menu

Strona 124 - Boot Settings Menu

Chapter 4 Configuring and Using BIOS Firmware 4-113. Move down the list, select the Change Supervisor Password or Change UserPassword option, and pres

Strona 125 - Boot Device Priority Menu

ixFiguresFIGURE 1-1 Sun Netra CP3220 Dual-Core Blade Server (Front View) 1–4FIGURE 1-2 Sun Netra CP3220 Quad-Core Blade Server (Front View) 1–5FIGURE

Strona 126 - Change Password Settings Menu

4-12 Sun Netra CP3220 Blade Server User’s Guide • January 20104.7 Updating the BIOSWhen they become necessary, updated BIOS images will be available a

Strona 127 - Chipset Main Menu

Chapter 4 Configuring and Using BIOS Firmware 4-13For example:3. To boot the blade server from the Shelf Manager, type:Note – Once the blade server is

Strona 128

4-14 Sun Netra CP3220 Blade Server User’s Guide • January 20104.11 Power-On Self-TestThe system provides a rudimentary power-on self-test (POST) that

Strona 129 - Appendix B BIOS Screens B-15

Chapter 4 Configuring and Using BIOS Firmware 4-154. On the Boot Settings Configuration screen (FIGURE B-17), you can enable ordisable the options sho

Strona 130 - Exit Options Menu

4-16 Sun Netra CP3220 Blade Server User’s Guide • January 2010

Strona 131 - Appendix B BIOS Screens B-17

5-1CHAPTER5Hardware ArchitectureThis chapter provides information about the hardware architecture.This chapter contains the following topics: Section

Strona 132

5-2 Sun Netra CP3220 Blade Server User’s Guide • January 20105.1 Block DiagramFIGURE 5-1 Block Diagram

Strona 133

Chapter 5 Hardware Architecture 5-35.2 The AMD Opteron ProcessorAMD Opteron processors with Direct Connect Architecture include several newfeatures, i

Strona 134

5-4 Sun Netra CP3220 Blade Server User’s Guide • January 2010FIGURE 5-2 AMD Opteron Processors Block Diagram5.3 MemoryThe Sun Netra CP3220 blade serve

Strona 135

Chapter 5 Hardware Architecture 5-55.4 Networking and I/ONetworking and I/O are provided by the following chips and interconnects: nVidia MCP55 (sout